Monnit Serial MODBUS Guia do Utilizador Página 10

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 12
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 9
Temperature DATA_0: INT16, SIGNED. Data is recorded in Celsius.
Divide data by 10 to get degrees Celsius out to one
decimal point.
Example: Data=271. 271/10 = 27.1°C
DATA_1, DATA_2, DATA_3 are not used.
Water DATA_0: UINT16, UNSIGNED. Data is recorded as 0
for no water present and 1 for water present in default
operation.
DATA_1, DATA_2, DATA_3 are not used.
Open / Closed DATA_0: UINT16, UNSIGNED. Data is recorded as 1
for magnet present and 0 for magnet absent in default
operation.
DATA_1, DATA_2, DATA_3 are not used.
PIR DATA_0: UINT16, UNSIGNED. Data is recorded as 1 for
motion detection and 0 for no motion.
DATA_1, DATA_2, DATA_3 are not used.
Humidity DATA_0 is Temperature Data, INT16, UNSIGNED.
DATA_1 is Humidity Data. INT16, UNSIGNED.
To convert the humidity and temperature to standard
units, apply the following math:
Temperature_C = (DATA_0 ÷ 100)
RH_% = (DATA_1 ÷ 100)
Example: DATA_0: 2374/100 = 23.74°C
DATA_1: 5289/100 = 52.89 %RH
DATA_2, DATA_3 are not used.
PAGE 10
Vista de página 9
1 2 ... 5 6 7 8 9 10 11 12

Comentários a estes Manuais

Sem comentários